Certifications & Standards: UL1778 (USA), cUL
(Canada), FCC Class A (emissions), NOM (Mexico), Conforms to IEEE
587 / ANSI C62.41 specifications
Additional Information:
2200VA / 1600 watt output capacity accommodates a variety of
server, networking and telecom devices
High power density 2.2kVA UPS system occupies only 106 square
inches of floorspace with a height of only 14.25 inches
Compatible with North American 120V / 60 Hz power as found in
the USA, Canada and Mexico
Offers 7 minutes runtime with a full load of 2200VA and 19
minutes with a half load of 1100VA
Line interactive voltage regulation corrects severe brownouts
and overvoltages from 79 to 147v back to normal 120v levels without
using battery power
9 total outlets (7 NEMA5-15R; 2 NEMA5-15/20R)
Includes NEMA 5-20 straight blade 20 amp input plug connection;
package includes optional user installable NEMA 5-15 input plug
connection
Notification of system status via 5 LEDs and multi-function
audible alarms
Included PowerAlert Software provides e-mail or pager
notification of power problems and the simultaneous automatic
unattended shutdown of multiple servers
4 built-in communications ports (2-DB9, 2-USB) for remote
monitoring and unattended shutdown
Slot for SNMP/web card (part#: SNMPWEBCARD) and environmental
sensor (part#: ENVIROSENSE) for remote communications in large IP
environments
Supports Tripp Lite's WatchDog software application to restore
unresponsive programs by automatically restarting them and
rebooting completely locked computers by automatically switching
UPS power off and back on again
Communication ports support on battery, low battery, power
restored, AC line voltage, DC battery voltage, load percentage,
battery charge current, battery capacity, internal UPS temperature
and line frequency status messaging. Interface supports timed
inverter shutoff after unattended shutdown, activate self-test and
10 second reboot of connected equipment
3 pairs of customized load management receptacles can be
individually powered off and back on again via software interface
to reboot remote equipment or automatic "load shedding" of less
critical loads to extend battery runtime for the most critical
equipment
Built-in Emergency Power Off (EPO) interface supports emergency
shutoff in large facilities
Hot-swappable / user replaceable batteries allow on-site
battery replacement through the front panel without powering off
connected equipment or removing the UPS from the rack
UPS battery set ships fully assembled and ready for use, no
time consuming, connection of individual internal batteries by user
is necessary
UL (USA), cUL (Canada), NOM (Mexico), FCC Class A
$250,000 Ultimate Lifetime Insurance. No warranty cards
required for coverage!
2 year manufacturers product warranty
Battery Information
Maximum Battery Recharge Time: 4 Hour
Backup/Run Time (Half Load): 19 Minute
Backup/Run Time (Full Load): 7 Minute
Battery Life: 6 Year
Battery Chemistry: Sealed Lead Acid
Hot Swappable: Yes
Management
Network Management: SNMP Manageable
Alarm:
On Battery
Overload
Low Battery
Power Description
Load Capacity (VA): 2200 VA
Load Capacity (Watt): 1600 W
Input Voltage: 110 V AC
Output Voltage: 120 V AC
Controls/Indicators
Status Indicators: Includes 5 front panel LEDs
to indicate BATTERY CHARGE LEVEL, AC LINE POWER STATUS, VOLTAGE
REGULATION STATUS, UPS LOAD LEVEL and BATTERY LOW / REPLACE
information